Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T13CM06530
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2014 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/29/2014 | BUILDING ABOVE CEILING | Approved | 1. LINESETS MISSING GROMETS AND INSULATION 2. HOT WATER LINES NOT INSULATED 3. PVC VENTING NOT PROPERLY SUPPORTED 4' MAX HORIZ |
|
05/27/2014 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
05/27/2014 | BUILDING ABOVE CEILING | Partial Approval | OPS AREA OK |