Permit: T13CM06448

Parcel: 12108027A


Addresses:

6125 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
10/16/2014 FIRE - KITCHEN EXH HOOD FINAL Approved 1. Tested Electrical shut down under hood. Tested Okay.
10/13/2014 FIRE - KITCHEN EXH HOOD FINAL Cancelled Called contractor (Brian-623-329-8359) first found out if they are ready stated not ready so he cancelled.
10/09/2014 FIRE - KITCHEN EXH HOOD FINAL Denied Electrical did not shut off under hood
10/08/2014 FIRE - KITCHEN EXH HOOD FINAL Denied Ansul system did not sound alarm
Electrical did not shut off under hood