Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2014 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 PSI test for 2 hours approved - all UG tested | |
| 07/31/2014 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | 1. saw all the pipe except for 10 ft to tie into the water main. 2. 200 lb test ok on this portion 3. need another 200lb test when tie in is done. |