Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/2014 |
MECHANICAL - FINAL |
|
Approved |
PER SIGNED JOB CARD |
| 10/17/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 10/17/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
PROVIDE A LETTER FROM ENGINER TO USE BRASS BACK FLOW PIPE OVERFLOW FROM SOFTNER. PROVIDE COPPER DRAINER PROVIDE THE GASKET AT EXAUST FAN PROVIDE STERLIZATION REPORT PROVIDE GREAS RECEPTOR AT HOOD PROVIDE HEAT SENSOR TEST |
| 10/16/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 10/13/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |