Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/2014 |
PLUMBING - ABOVE CEILING |
|
Approved |
PER SIGNED JOB CARD |
| 10/16/2014 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 10/16/2014 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IMMEDIATELY INSTALL TEMPERORY VALVES AT ALL HAND SINKS. WATER IS DANGERSLY HOT! SORCE P9P4.0 SECURE MV'S AT LAVS PROVIDE BACKFLOW ASSEMBLES & DEVICES SHOWN AON P-6 REPLACE ALL DAMAGED CO PLUGS LISTED TO REMOVE A PLUG PIPE SOFTNER OVER FLOW DRAIN, PROVIDE AIR LAP PROVIDE L CU INDIRECT WASTE PIPING AS SPECIFIED MP2 PROVIDE LISTED CO ADDAPTOR IN CONCRET WALK WAY INSTALL GAS REGULATORS W/ VENTS DOWN AS REQUIRED PER INSTALL INSTRUCTIONS TO PREVENT MOISTURE INSTALL ALL THERMOTURES SHOWN ON WH DETAIL CORRECT HEALTH HAZORDS AT URINAL VACUUM BREAKER PROVIDE PROPER CONNECTION AT MS SOAP DISP. AAV MAY NOT HAVE VALVES DOWN STREAM PROVIDE STERLIZATION DOCUMANTATION |
| 10/08/2014 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 09/12/2014 |
PLUMBING - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |
| 09/12/2014 |
PLUMBING - ABOVE CEILING |
|
Partial Approval |
COMPLETE INSULATION |
| 08/26/2014 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 08/21/2014 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |