Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2014 | BUILDING - FINAL | Approved | PER SIGNED JOB CARD | |
| 10/17/2014 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/17/2014 | BUILDING - FINAL | Partial Approval | PROVIDE A LETTER FROM ENGINER TO USE BRASS BACK FLOW PIPE OVERFLOW FROM SOFTNER. PROVIDE COPPER DRAINER PROVIDE THE GASKET AT EXAUST FAN PROVIDE STERLIZATION REPORT PROVIDE GREAS RECEPTOR AT HOOD PROVIDE HEAT SENSOR TEST | |
| 10/16/2014 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/16/2014 | BUILDING - FINAL | Partial Approval | FINISH WORK FROM PREVIOUS REPORT: EF-2 HAS ELEC ISSUES NEED CAPTURE & CONTAINMENT, HEAT SENSOR TEST REPORTS | |
| 10/13/2014 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/13/2014 | BUILDING - FINAL | Partial Approval | PROVIDE AIR BALANCE REPORT CAPTURE AND CONTAINMENT TEST, HEAT SENSOR TEST STERILIZATION REPORT BACKFLOW CERTS. PROVIDE AN INSULATION SHIELD AT WTR HTR VENT. PROVIDE LISTED GASKET AT EXHAUST FAN. PROVIDE A ROOF JACK AT ELEC TO CONDENSOR. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. PROVIDE DRAFT HOODS FOR HEATERS. PROVIDE TEST FOR CO2 SENSORS |