Permit: T13CM06437

Parcel: 11106006C

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/21/2014 BUILDING - FINAL Approved IVRS - Inspection :*
02/19/2014 BUILDING - FINAL Partial Approval IVRS - Inspection :*
02/19/2014 BUILDING - FINAL Partial Approval LABELS FALLING OFF PANEL. SEAL CO PLUG & AAV. INSTALL AN APPROVED PIPE SUPPORT, MIN 1" CLEARANCE REQ AT WH VENT.
01/16/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
01/16/2014 BUILDING - FINAL Not ready for Inspection LABEL ELECTRICAL PANEL CIRCUIT BREAKERS. NEW PLUMBING FOR KITCHEN SINK REQUIRES A PERMIT REVISION AND CODE CORRECTIONS. PROPER USE OF DRAINAGE FITTINGS. ALSO, ABS MAY NOT BE EXPOSED TO SUN. WATER HEATER REQUIRES CLEARANCE FROM COMBUSTIBLES AND PROPER RELIEF VALVE TERMINATION. SEAL ROOF PENETRATIONS. CARBON MONOXIDE DETECTOR REQUIRED.
01/15/2014 BUILDING - FINAL Partial Approval IVRS - Inspection :*
01/15/2014 BUILDING - FINAL Partial Approval SMOKE DETECTOR INSTALLED WITHIN 3' OF SUPPLY AIR VENT. RELOCATE DETECTOR OR ADD ANOTHER DETECTOR IN THE PROPER LOCATION
01/08/2014 BUILDING - FINAL Partial Approval IVRS - Inspection :*