Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13CM06341

Parcel: 136061570

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM06341

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2014 FIRE - FINAL Approved
01/06/2014 FIRE - FINAL Partial Approval Okay to stock no sales or public in building
1008.1.1 Size of doors
1. Rear exit door from non-sales #2 (as stated on plans) does not meet the minimum width requirement of 32" inches (28"inches) install a bigger door or have leaf section open with main door no slide bnolt locks allowed.
2. Both exit doors that are removed out of service, shall cover doors on the inside so as not to show as a door and label on the outside of the doors with the following "THIS DOOR BLOCKED" 6 inch letters.
3. Need to label riser room door with the following; "RISER ROOM"
4. 2 battery back lights on sales floor failed to work repair or replace.