Inspection History: FIRE - FINAL
Permit Number - T13CM06341
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2014 | FIRE - FINAL | Approved | ||
01/06/2014 | FIRE - FINAL | Partial Approval | Okay to stock no sales or public in building 1008.1.1 Size of doors 1. Rear exit door from non-sales #2 (as stated on plans) does not meet the minimum width requirement of 32" inches (28"inches) install a bigger door or have leaf section open with main door no slide bnolt locks allowed. 2. Both exit doors that are removed out of service, shall cover doors on the inside so as not to show as a door and label on the outside of the doors with the following "THIS DOOR BLOCKED" 6 inch letters. 3. Need to label riser room door with the following; "RISER ROOM" 4. 2 battery back lights on sales floor failed to work repair or replace. |