Permit: T13CM06341

Parcel: 136061570

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
01/08/2014 FIRE - ALARM FINAL Approved
01/06/2014 FIRE - ALARM FINAL Denied Tested dailer monitoring comapny did get singals for tamper and flow but no sounding in riser room as to if the device is working, needs to have a sounder when in use called Simplex they need to add a sounder and get a permit for this install.
01/02/2014 FIRE - ALARM FINAL Denied 1. Simplex not finished installing dialer.