Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
06/22/2015 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
04/23/2015 MECHANICAL - PROGRESS Not ready for Inspection IVRS - Inspection :*
04/23/2015 MECHANICAL - PROGRESS Not ready for Inspection 1. PROVIDE SEISMIC RESTRAINTS AT REGISTERS
2. DUCT JOINTS NOT SEALED
3. CONDENSATE NOT COMPLETE
4. WIRING NOT COMPLETE AT I.T. ROOM
5. PROVIDE MEANS OF DISCONNECT AT MINI-SPLIT
6. PROVIDE FILTER ACCESS