Permit: T13CM06259

Parcel: 110035930

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/25/2014 PLUMBING - INTERMEDIATE Approved
05/05/2014 PLUMBING - INTERMEDIATE Partial Approval 150 PSI TEST ON REMAINDER OF MED GAS PIPING IS OK. OK TO COVER ELEC IN WALLS. STILL NEED TO SEE ELEC ABOVE SHEETROCK CEILINGS IN O.R. WILL CHECK THROUGH LIGHT WELLS. STILL NEED TO SEE SHOWERS.
04/25/2014 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/21/2014 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/21/2014 PLUMBING - INTERMEDIATE Partial Approval 150 PSI TEST ON MED GAS FOR PACU & PREOP OXYGEN & VACUUM IS OK. DISCUSSED TERMINATION MED GAS VENT TO ROOFTOP NEAR ROOF HATCH. CHECKED ELEC & PLUMBING IN EASTSIDE WALLS UP TO MIDDLE CORRIDOR. EXTERIOR WALLS OK TO FOAM