Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2014 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 05/05/2014 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
150 PSI TEST ON REMAINDER OF MED GAS PIPING IS OK. OK TO COVER ELEC IN WALLS. STILL NEED TO SEE ELEC ABOVE SHEETROCK CEILINGS IN O.R. WILL CHECK THROUGH LIGHT WELLS. STILL NEED TO SEE SHOWERS. |
| 04/25/2014 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 04/21/2014 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 04/21/2014 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
150 PSI TEST ON MED GAS FOR PACU & PREOP OXYGEN & VACUUM IS OK. DISCUSSED TERMINATION MED GAS VENT TO ROOFTOP NEAR ROOF HATCH. CHECKED ELEC & PLUMBING IN EASTSIDE WALLS UP TO MIDDLE CORRIDOR. EXTERIOR WALLS OK TO FOAM |