Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM06152
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2014 | FIRE - FINAL | Approved | ||
| 01/13/2014 | FIRE - FINAL | Denied | 1. Need annual fire sprinkler inspection completed. 2. Need 5 year check valve inspection completed. 3. Correct sprinkler coverage front of cooks window where wall to ceiling not painted sprinkler head blocked spray pattern. 4. Remove plastic bags on sprinkler heads in dining area 5. Need to label breakers for emergency lighting and exit signs so that we can test with power off for 20 minutes. When power was shut off found two back up lighting failed in dining are north side. 6. Mount fire extinguishers every 75 foot travel distance. 7. Need a fire department key box installed. |