Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/27/2014 | MECHANICAL - FINAL | Approved | SECURE BLOCKS W/ MASTIC TO ROOF. PAINT ALL PVC TO PROTECT AGAINST UV DAMAGE | |
| 11/01/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/01/2013 | MECHANICAL - FINAL | Denied | TIGHTEN LOOSE ELEC CONNECTIONS. CANNOT ACCESS ELEC DISCONNECT. SUPPORT PVC EVERY 4' & TERMINATE TO WITHIN 6" OF THE GROUND. BLOCK & CLAMP LOW VOLTAGE ELEC CONDUIT. 96,000 BTU FURNACE REQUIRES 3/4" PIPE 80' FROM METER. OK TO CHANGE TE4E IN CLOSET TO 3/4X3/4X1/2. PROVIDE A TEST ON ALL NEW PIPING. |