Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/10/2014 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 01/07/2014 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 01/07/2014 |
PLUMBING - FINAL |
|
Partial Approval |
PROVIDE CHLORINATION REPORT AND AIR BALANCE REPORT. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. PERMANENTLY I.D. ALL EQUIPMENT ON ROOF. CONDENSING UNIT OVERFUSED. PROVIDE A PERMIT FOR NEW A/C UNIT. GAS FLEX NOT ADEQUATE. PROVIDE FRESH AIR INTAKE FOR NEW A/C UNIT. AIR BALANCE TO INCLUDE OUTSIDE AIR AS PER PLANS & MAKEUP AIR AS PER PLANS. A/C UNITS OVERFUSED. |
| 12/31/2013 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |