Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2014 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 05/19/2014 |
MECHANICAL - FINAL |
|
Approved |
CORRECTIONS HAVE BEEN MADE. AIR BALANCE OK. |
| 05/15/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 05/15/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
FINISH MARKING DATA PLATES. FINISH FRESH AIR INTAKES. PROVIDE 10' CLEARANCE FROM FRESH AIR NEAR PLUMBING VENTS. FINISH CONDENSATE PIPING & SUPPORTS. PROIVDE SECONDARY OVERFLOW SENSOR AT FAN COIL. CONDENSATE DRAIN HOSE IS KINKED AT TERMINATION. PROVIDE A HOSE CLAMP AT TERMINATION. PROVIDE AIR BALANCE REPORT FOR OUTSIDE AIR. |
| 05/14/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 05/14/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
PERMANENTLY I.D. ALL A/C EQUIPMENT. MARK UNIT DATA PLATES & FUSE ACCORDINGLY. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. SOME TRAPS ARE BACKWARDS. |