Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM05890
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2014 | FIRE - FINAL | Approved | ||
01/15/2014 | FIRE - FINAL | Denied | Same exit signs failed battery back up test over door 101 & 113A per approved plans | |
01/13/2014 | FIRE - FINAL | Denied | 1. Corridor #116 exit sign over door # 101 backup power failed. 2. Exit over door # 113A back up power failed. 3. Address number posted above entrance door 3 inch size |