Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2014 |
BUILDING - FINAL |
|
Approved |
FIRE APPROVED 01/16/14 |
| 01/15/2014 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 01/15/2014 |
BUILDING - FINAL |
|
Partial Approval |
PENDING FIRE |
| 01/13/2014 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 01/08/2014 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 01/08/2014 |
BUILDING - FINAL |
|
Not ready for Inspection |
CONDENSATE PIPING ON ROOF DOES NOT SLOPE 1/8" PER FT. PROVIDE A ROOF JACK AT PENETRATION THROUGH ROOF. BLOCK & CLAMP PVC EVERY 4'. PAINT EXPOSED PVC. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. GROUNDING ELECTRODE CONDUCTOR HAS BEEN VANDALIZED. TESTED EM LIGHTING. AIR BALANCE OK. |