Permit: T13CM05861

Parcel: 12509141A


Addresses:

2901 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/03/2014 FIRE - FINAL Approved
12/27/2013 FIRE - FINAL Partial Approval Temp C of O approved for training only no public for final the following will needed:
1. Egress back up lighting needed on both exits outside
2. Change two painted sprinkler heads in basement by entrance door
12/18/2013 FIRE - FINAL Denied Under 901.6 sprinkler code: (SPRINKLER ONLY IN THE BASEMENT)
1. Annunal sprinkler inspections are pass due 07/07/2009
2. 5 year check valve pass due
3. Shall replace all painted sprinkler heads
4. Repair broken brace on the end of the 1 inch branch line
5. Repair or replace the FDC