Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2013 | ELECTRIC - RECONNECT | Approved | ||
| 10/07/2013 | ELECTRIC - RECONNECT | Not ready for Inspection | INSPECTOR PLEASE RECHECK DISTANCE FROM TRANSFORMER TO PANEL. CUSTOMER STATES 43' LINEAL, WHICH WOULD PROVIDE MORE THAN 45' UG. 10kAIC IS ACCEPTABLE FOR UNDERGROUND FEEDS 45' FROM TRANSFORMER. | |
| 10/03/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/03/2013 | ELECTRIC - RECONNECT | Denied | SERVICE TO BE PUT BACK TOGETHER & MAIN BREAKER AIR RATING ON BREAKER TO BE 22,000 |