Permit: T13CM05818

Parcel: 12515118A


Addresses:

3227 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T13CM05818

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2014 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/23/2013 MECHANICAL - FINAL Denied NEXT FAILED INSPECTION WILL RESULT IN A REINSPECTION FEE
SECONDARY DRAIN CANNOT TERMINATE INTO THE PUMP. IT MUST BE CONSPICIOUS OR USE ON OVERFLOW SENSOR
HEAT STRIP STILL NOT MARKED ON DATA PLATE. GLUE ALL PVC FITTINGSD AND USE PURPLE PRIMER PRIOR TO GLUE
12/20/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/06/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/06/2013 MECHANICAL - FINAL Denied DISCONNECT WITH FUSES STILL NOT ACCESSIBLE. PRIMARY DRAIN IS CONNECTED TO SECONDARY OUTLET. PROVIDE AN OVERFLOW SENSOR IN SECONDARY OUTLET. MARK FAN COIL DATA PLATE W/ PROPER HEAT STRIP & FUSE ACCORDINGLY. SECURE DISCONNECT BEHIND WATER HEATER.
10/25/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/25/2013 MECHANICAL - FINAL Denied 1. PROVIDE SECONDARY DRAIN AT AC COIL
2. A/C DISCONNECT NOT APPROED LOCATION
3. COND PUMP NOT WIRED CORRECTLY
4. PROVIDE GASKET AT DOOR SEPERATE RETURN AIR
10/18/2013 MECHANICAL - FINAL Cancelled IVRS - RI canceled
10/18/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*