Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/26/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/26/2013 | BUILDING - FINAL | Denied | CONTINUED DENIED INSPECTIONS WILL RESULT IN A REFEE. CORRECT TUB SPOUT. ID HOT WIRES @ BREAKER. TIGHTEN CONNECTIONS. INSTALL BUSHING. SEAL WALL PENETRATIONS. STILL HAVE OPEN GROUND. GFI NOT WORKING. | |
| 11/21/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/21/2013 | BUILDING - FINAL | Not ready for Inspection | WH & FURNACE VENT. SINGLE WALL REQ 6" CLEARANCE. INSTALL IN PROPER DIRECTION OF FLOW. MISSING SLIP NUT ON LAVATORY DRAIN. WCS NOT SEALED AT FLOOR CONNECTION. MISSING HB VACUUM BREAKERS. OPEN GROUND AT CLOSET OUTLET. ALSO, CORRECT COVER. ROOF ACCESS. | |
| 11/08/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/08/2013 | BUILDING - FINAL | Not ready for Inspection | COMPLETE ALL WORK. WATER HEATER VENT TOUCHING WOOD, ALSO, SUPPORT PIPING. HOSE BB VACUUM BREAKERS REQUIRED FOR SAFETY. PROVIDE LISTED FITTINGS. TRAP ARMS MAY NOT CHANGE ELEVATION (ALL LOCATIONS). OPEN GROUND ON OUTLETS. LABEL PANEL. PROVIDE ROOF ACCESS. ALL FIXTURES TO BE OPERATIONAL. NEW KIT SINK SHALL BE SEALED & SECURED AND LISTED DRAIN PARTS. SECURE DW HOSE. ANTI TIP. INSP STOPPED. | |
| 10/16/2013 | BUILDING - FINAL | Not ready for Inspection | NEED TO INSPECT WH AT FINAL |