Permit: T13CM05777

Parcel: 127121540


Addresses:

5756 E 6TH ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/03/2013 BUILDING - FINAL Approved IVRS - Inspection :*
11/26/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/26/2013 BUILDING - FINAL Denied CONTINUED DENIED INSPECTIONS WILL RESULT IN A REFEE. CORRECT TUB SPOUT. ID HOT WIRES @ BREAKER. TIGHTEN CONNECTIONS. INSTALL BUSHING. SEAL WALL PENETRATIONS. STILL HAVE OPEN GROUND. GFI NOT WORKING.
11/21/2013 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
11/21/2013 BUILDING - FINAL Not ready for Inspection WH & FURNACE VENT. SINGLE WALL REQ 6" CLEARANCE. INSTALL IN PROPER DIRECTION OF FLOW. MISSING SLIP NUT ON LAVATORY DRAIN. WCS NOT SEALED AT FLOOR CONNECTION. MISSING HB VACUUM BREAKERS. OPEN GROUND AT CLOSET OUTLET. ALSO, CORRECT COVER. ROOF ACCESS.
11/08/2013 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
11/08/2013 BUILDING - FINAL Not ready for Inspection COMPLETE ALL WORK. WATER HEATER VENT TOUCHING WOOD, ALSO, SUPPORT PIPING. HOSE BB VACUUM BREAKERS REQUIRED FOR SAFETY. PROVIDE LISTED FITTINGS. TRAP ARMS MAY NOT CHANGE ELEVATION (ALL LOCATIONS). OPEN GROUND ON OUTLETS. LABEL PANEL. PROVIDE ROOF ACCESS. ALL FIXTURES TO BE OPERATIONAL. NEW KIT SINK SHALL BE SEALED & SECURED AND LISTED DRAIN PARTS. SECURE DW HOSE. ANTI TIP. INSP STOPPED.
10/16/2013 BUILDING - FINAL Not ready for Inspection NEED TO INSPECT WH AT FINAL