Permit: T13CM05749

Parcel: 12801033A


Addresses:

6211 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T13CM05749

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2014 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/25/2014 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/14/2014 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/14/2014 ELECTRIC - INTERMEDIATE Partial Approval 240-120 delta hot leg b
01/13/2014 ELECTRIC - INTERMEDIATE Denied 1. BOND WATER/GAS PIPING
2. GROUNDING ELECTRODE CONDUCTORS NEED TO BE TIED TOGETHER UFER AND GROUND RODS
3. BOND BUSHINGS ON SUPPLY SIDE OF SERVICE CONDUCTORS/RACEWAYS
4. R-PINS IN MAIN SERVICE DISC SWITCHES
5. HI LEG DELTA- BPHASE
01/10/2014 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/09/2014 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/09/2014 ELECTRIC - INTERMEDIATE Not ready for Inspection NO INSPECTION