Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T13CM05721
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2014 | ELECTRIC - FINAL | Approved | ||
04/29/2014 | ELECTRIC - FINAL | Not ready for Inspection | #28 ENERGIZED NEUTRAL TERMINATE CONDUCTORS CORRECTLY NEED SINGLE POLE 30 AMP NOT 2 POLE #30 60 AMP BREAKER ON 50 AMP PLUG CLEAN SURFACE BEHIND GROUND BAR #31 60 AMP BREAKER ON 50 AMP PLUG USE MANUFACTURERS APPROVED BREAKER #26 NEED ISOLATED NEUTRAL BAR KO SEAL SERVICE MASTER MAIN LABEL BREAKERS CORRECT SIZED BREAKERS TRIMED CONDUCTORS #32 CLEAN GROUND BAR SURFACE MISSING COVER HARDWARE #33 CLEAN SURFACE UNDER GROUND BAR #34 NOT READY #35 NO PROGRESS #36 FINISH TRIPLEX REPAIRS CLEAN SURFACE UNDER GROUND BAR |
|
03/28/2014 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/28/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/28/2014 | ELECTRIC - FINAL | Denied | - NEW SERVICE AT #34 HAS GROUDNING ELECTRODE SYS. RATED AS SERVICE EQUIP ONLY. CANNOT BE USED AS SUBPANEL. FED FROM MAIN PARK SERVICE. - THERE ARE STILL OTHER CODE VIOLATIONS THROUGHOUT; UNSUPPORTED PANELS, SPLICES COMING APART, ETC... - HAVE CALL INTO LEE RAY FOR QUESTIONS |
|
01/22/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/22/2014 | ELECTRIC - FINAL | Partial Approval | - INSPECTION WITH CONTR ON SITE - NO UNIT INSPECTIONS, ONLY TO MH SERVICE DISCONNECT - OK 3 NEW POLES REPLACED & SERVICE AT UNIT #34, HOWEVER, SERVICE HAS NO GROUNDING ELECTRODE SYSTEM. |
|
12/17/2013 | ELECTRIC - FINAL | Partial Approval | MET WITH ELECTRICAL CONTRACTOR ON SITE. THERE HAVE BEEN SOME REPAIRS TO THE DISTIBUTION SYSTEM, BUT THERE ARE STILL 3 POLES THAT NEED TO BE REPLACED AND AT LEAST ONE SERVICE. ABSOLUTELY NO INSPECTIONS WERE DONE INSIDE ANY OF THE DWELLING UNITS. THIS INSPECTION ONLY COVERED SITE DISTRIBUTION. CONTRACTOR INDICATED THAT OWNER WOULD BE ELIMINATING THE MASTER / SUB-METERED SYSTEM WITH NEW UNDERGROUND SERVICES FROM TEP IN THE NEAR FUTURE. |
|
10/10/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/10/2013 | ELECTRIC - FINAL | Partial Approval | ELECT CONTR ON SITE, DOES NOT HAVE PLANS OR PERMIT. CONTR TO RESCH INSPECTION WITH PDSD & CODE ENFORCEMENT AS PER NOTES FOR LOCKS, HOLDS, & NOTICES. |