Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T13CM05721
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2014 | ELECTRIC - PROGRESS | Approved | ||
05/19/2014 | ELECTRIC - PROGRESS | Partial Approval | #34 NEED MANUFACTURERS HOLD DOWN #37 NEED APPROVED COVER #40 SHEET METAL SCREWS NOT FOR GROUND BAR HOUSE 53 SPLICES UNDER PORCH #17 NEED APPROVED METER SEAL COVER #30 MISSING DEAD FRONT #28 MISSING DEAD FRONT |
|
04/29/2014 | ELECTRIC - PROGRESS | Denied | #50 PREPARE FOR CLEARANCE | |
04/10/2014 | ELECTRIC - PROGRESS | Denied | #50. 1. Used green wire and covered with tape for the neutral wires- not allowed need white wire. Inspection done on 4-3-14 with correction needs for approval. 2. Breaker not labeled. 3. Conduit added to side of panel not sealed and required at the location placed. 4. Drop has not been changed and has single phase going to panel leaving all the breakers on same phase. #27. 1. Interior panel used for the exterior and has fuses and needs exterior type panel with breakers. 2. GFCI not installed on the exterior outlets near the exterior panels. 3. Has an outlet near the metal shed and not GFCI. #52. 1. Has an extension cord along the chain link fencing to appliances with a muti-plug attached for other items to be connected as lighting and using power tools. 2. Wire size is too small for the feed to the panel for the unit. #28. 1. Lacking the dead front. 2. The lifeline is an extension cord and connected direct. #29. 1. New pole has been spiced and has straps and should have been continued as one solid pole. 2. Cover plate lacking on junction box. 3. Panel not labeled. 4. Lifeline connected direct. 5. Electrical support not on new pole. #30. 1. Dead front lacking. 2. Washer machine and dryer has wiring added and buried in the ground and not UF type with a plastic box and placed on the exterior of the mobile home. 3. Wrong straps for the riser on the pole. #31. 1. Wrong breaker for the panel for disconnecting power. #26. 1. Lacking the grounding. 2. Life line connected direct. Master panel near the trailer #24 1. Wires have been trimmed for the grounding conductor and at the breaker. 2. Wire nuts are the wrong size for the size of wire being connected. 3. Anti-oxide compound not used on all Aluminum wiring. 4. Label of breakers. 5. Wrong color wiring used on some of the wiring for the neutrals use to feed power. #23. 1. Double lugging on the disconnect. #32. 1. MC cable being used for the dyer and the washer machine outlets. 2. Double lugging. 3. Seal tight not strapped on the exterior wall. #31. 1. Metal shed has power to the interior with a light and outlet. #33. 1. Grounding and neutrals are mixed on the same bar. Separate. #34. 1. Wrong panel used for the meter, which is a service panel and requires a sub-panel. #35. 1. Remove light on the top of the door on a zip cord and place the proper lighting for the door opening. 2. Extension cord used for the lifeline. #36. 1. Dead front is wrong type that has been added to the panel. 2. Grounding and neutrals are mixed. Separate. 3. Cut wires that are not protected and leave open conductors. 4. Supply lines on the poles are spliced with a split bolt and have more than 2-wires. #37. 1. Wrong fuses and type being used to outlet in the box. 2. Grounding and neutrals mixed. #38. 1. Life line cord into the cap not proper. Note: On the areas where connectors are being for splices they did not use rubber tape and only using electrical tape. #40. 1. Grounding and neutrals mixed. #41. 1. Support pole has been spliced and using metal bracing to keep together. 2. Dead front is wrong type. 3. Grounding and neutrals mixed. Separate. #53. 1. Romex on the roof and not protected. 2. The feed wires are lying on the roof on the southeast side by the porch. 3. Remove wiring to sign in the front of the property with the lighting for interior use. 4. Has wiring that has been spliced under the porch. #42. 1. Dead front is lacking the portion of fuses, outlets 2. The pull out has a broken handle. #43. 1. Dead front is lacking. 2. Life line is connected direct into the box. #47. 1. Wrong outlet type for the box for the lifeline. #44B 1. Lifeline is rated for 30 AMP and the breaker is for 50 AMP. #45. 1. Main panel are lacking the blank covers where the breaker has been removed. 2. Double tap on the 200 AMP panel. 3. Remove dead outlet near the cooler. 4. Exterior outlets not GFCI for the light on an extension cord. #3. Meter ring bent and broken. Note: All panel or outlet boxes need to be labeled for what unit it supplies power to. |