Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/27/2014 |
FIRE - FINAL |
|
Approved |
|
| 01/22/2014 |
FIRE - FINAL |
|
Not ready for Inspection |
Still waiting for revised Evacuation Plan. Plan submitted was for the wrong location. |
| 01/09/2014 |
FIRE - FINAL |
|
Denied |
Please provide the Fire Safety and Evacuation plan for this Group I occupancy per Section 404 of the 2012 IFC. Make sure the provisions of IFC 1008.1.9.6 are covered, especially items 5-7. |
| 12/09/2013 |
FIRE - FINAL |
|
Denied |
Need to show proof that two doors in the 1 hour wall are 20 minute fire rated doors and have fire approved hardware on doors i.e., hinges, door handles, panic hardware, door frame. |