Permit: T13CM05705

Parcel: 11108314B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/27/2014 FIRE - FINAL Approved
01/22/2014 FIRE - FINAL Not ready for Inspection Still waiting for revised Evacuation Plan. Plan submitted was for the wrong location.
01/09/2014 FIRE - FINAL Denied Please provide the Fire Safety and Evacuation plan for this Group I occupancy per Section 404 of the 2012 IFC. Make sure the provisions of IFC 1008.1.9.6 are covered, especially items 5-7.
12/09/2013 FIRE - FINAL Denied Need to show proof that two doors in the 1 hour wall are 20 minute fire rated doors and have fire approved hardware on doors i.e., hinges, door handles, panic hardware, door frame.