Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2013 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 10/02/2013 |
MECHANICAL - FINAL |
|
Approved |
CORRECTIONS HAVE BEEN MADE |
| 09/25/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 09/25/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
INSTALL 3 X 4 REDUCER ON THE FURNACE OUTLET. PROCIDE DOUBLE WALL VENTING UNTIL 6" BEYOND COMBUSTIBLE DOOR JAM & DOOR. SINGLE WALL REQUIRES 6" CLEARANCE. DOUBLE WALL REQUIRES 1" CLEARANCE, NORTH UNIT. SOUTH UNIT NEEDSE 4" X 3" DOUBLE WALL REDUCER. YOU CANNOT RUN DOUBLE WALL TO SINGLE WALL. |
| 09/18/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 09/18/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
PROVIDE MIN 6" CLEARANCE TO COMBUSTIBLES NEAR VENT CONNECTOR. PROVIDE TAMPER-PROOF CAPS ON SERVICE PORTS AT CONDENSORS. |