Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/12/2014 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/12/2014 | ELECTRIC - SERVICE UPGRADE | Denied | 1. PROVIDE BUSHING ON FITTING WHERE SERVICE CONDUCTORS PASS THRU COMPARTMENTS. 300.4 352.46 NEC 2. HUB AT CONDUIT RISER TERMINATION MUST BE GROUNDING TYPE FOR SUPPLY SIDE OF SERVICE 3. GROUND RODS MUST BE 6' MIN APART 4. GROUNDING ELECTRODE CONDUCTOR TO BE 1/0 CU PER 250.66 NEC 5. INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE |