Permit: T13CM05628

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM05628

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2014 FIRE - FINAL Approved
07/30/2014 FIRE - FINAL Denied 1. Add baffles on sprinkler heads over bar area (6).
2. Need dry pendent sprinkler head ¾" in keg cooler by entrance door okay to use ½" dry pendent until ¾" pendent comes in.
3. Test Em lighting over main entrance door
07/29/2014 FIRE - FINAL Denied 1. Install 6 fire extinguishers 2A-10BC type 75 foot travel distance
2. 2 emergency lights failed one on the dinning floor and one over rear kitchen exit door
3. 1 exit sign failed hallway to rear kitchen exit door
4. Need as built for changes on plans need to bubble all changes on plans and call out what was done, redo flow points for all changes.
5. Change out all seals on nozzles and use proper lube.
Install 4 K class fire extinguishers in kitchen 2 for the proper coverage of all appliances under the hoods and 2 are needed for the amount of oil in the deep fryers totaling of 120 pounds.
6. Need to check outside back up lighting over the main entrance roof was not installed at time of inspection
7. Post Occ load sign by main front door inside dinning 403, patio dinning 59 and kitchen 18