Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13CM05628
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2014 | FIRE SPKLR - FINAL | Approved | ||
07/30/2014 | FIRE SPKLR - FINAL | Denied | 1. Add baffles on sprinkler heads over bar area (6). 2. Need dry pendent sprinkler head ¾" in keg cooler by entrance door okay to use ½" dry pendent until ¾" pendent comes in. |