Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2013 | ELECTRIC - FINAL | Approved | ||
| 09/13/2013 | ELECTRIC - FINAL | Partial Approval | 1. INSIDE HOUSE OK; SMOKIES, CO DETECTOR OK 2. FEEDER WIRES MUST BE INSTALLED TO MAIN LUG 3. FEED FROM WEATHERHEAD DOWN MUST BE SIZED FOR 100A |
|
| 09/12/2013 | ELECTRIC - FINAL | Denied | 1. FEED FROM METER CAN TO PANEL MUST BE INSTALLED 2. VERIFY FEEDER SIZE FROM WEATHER HEAD TO METER CAN IS SUFFICIENT FOR 100A MAIN 3. NEED TO ACCESS INSIDE OF HOUSE TO VERIFY SAFETY OF WIRING |