Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2013 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/17/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/17/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. NO GFI AT FRIDGE 2. PROVIDE CLAMP AT KITCHEN LIGHT WIRING 3. ROMEX NOT TO BE EXPOSED 4. SMOKE ALARMS TO BE A MIN OF 3' FROM VENTS 5. LOCATE RANGE HOOD WIRING IN APPROVED LOCATION 6. PROVIDE 2 GROUND RODS 6' APART, PROVIDE BONDING TO GAS AND WATER |