Permit: T13CM05559

Parcel: 132111200

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/30/2013 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/17/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/17/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. NO GFI AT FRIDGE
2. PROVIDE CLAMP AT KITCHEN LIGHT WIRING
3. ROMEX NOT TO BE EXPOSED
4. SMOKE ALARMS TO BE A MIN OF 3' FROM VENTS
5. LOCATE RANGE HOOD WIRING IN APPROVED LOCATION
6. PROVIDE 2 GROUND RODS 6' APART, PROVIDE BONDING TO GAS AND WATER