Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T13CM05558
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2017 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 12/20/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 12/20/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1. 400 A PANEL OK TO ENERGIZE 2. 2-2"CONDUITS OK TO COVER 3.RE CALL WHEN DOUBLE RISER IS COMPLETED 4. UNAPPROVED WIRE USED FOR SERVICE SHOULD BE CHANGED |