Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2014 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 02/21/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 02/21/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
ROOFTOP CORRECTIONS OK. FAN REQ'S ADJUSTMENT |
| 02/19/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 02/19/2014 |
MECHANICAL - FINAL |
|
Denied |
PLAN SPECIFIES TYPE I GREASE DUCT, AS NEEDED, PROVIDE SMOKE TEST FOLLOWED BY FIRE WRAP OR REVISE. CORRECT EXHAUST FAN. CORRECT INSULATION AND PROTECT FROM UV. ADD SUPPORT AT EACH END OF HORIZ G DUCT. OK TO USE AS NON TYPE I AFTER SUPPORTS. |