Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T13CM05469
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/27/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/10/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/09/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/05/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/05/2013 | ELECTRIC - FINAL | Not ready for Inspection | 1. COMPLETE OPEN CIRCUITS 2. PROVIDE PROPER CLEARANCES FOR SUBPANEL IN BLDG 3. PROVIDE DOCUMENTATION OF APPROVED BUFFER GROUND 4. BONDING IN MAIN PANEL NOT PROPERLY ATTACHED |