Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM05386
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2014 | FIRE - FINAL | Approved | ||
01/15/2014 | FIRE - FINAL | Denied | No sprinkler work was needed or done on this permit work was only for outside patio and a door install on the south east corner of building only. 1. IFC & IBC 1008.1.9.3 New entrance doors being installed are required to open in one operation will need panic hardware on doors, no other locks allowed. 2. Need outside emergency backup lighting installed outside new doors. 3. In new patio on the westside need panic hardware on gates or gate open free style no latched or locks allowed. 4. Need exit signs posted by gates in new patio. |