Permit: T13CM05386

Parcel: 128100810


Addresses:

5470 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM05386

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2014 FIRE - FINAL Approved
01/15/2014 FIRE - FINAL Denied No sprinkler work was needed or done on this permit work was only for outside patio and a door install on the south east corner of building only.
1. IFC & IBC 1008.1.9.3 New entrance doors being installed are required to open in one operation will need panic hardware on doors, no other locks allowed.
2. Need outside emergency backup lighting installed outside new doors.
3. In new patio on the westside need panic hardware on gates or gate open free style no latched or locks allowed.
4. Need exit signs posted by gates in new patio.