Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2013 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 09/18/2013 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/18/2013 | PLUMBING - GAS PRESSURE TEST | Denied | 2.1 PSI ON GAUGE. CORRECT YOUR LEAK. INSTALL FLASHING OVER LARGER SLEEVE AND SECURE IT. ADD A SUPPORT TO ROOFTOP GAS PIPE NEAR SOV. | |
| 09/10/2013 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/10/2013 | PLUMBING - GAS PRESSURE TEST | Denied | PLEASE FIND AND CORRECT LEAK. CORRECT WH VENT CONNECTION AT 6". SUGGEST 3X6 INCREASER. BUSHING OR EXTEND 3" THRU 6" SLEEVE. TERMINATE 1' ABOVE AIR INTAKE. SUPPORT GAS PIPE AT SOV FOR FURNACE. INSTALL CARBON MONOXIDE DETECTORS OUTSIDE OF EACH SLEEPING AREA. RELIEF VALVE DRIPPING. |