Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2013 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :* |
| 12/05/2013 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
1. At the shower- horizontal dry vent not permitted per the IRC. 3" quarter bend not permitted horizontal X horizontal. Changes in direction in the building drain and sewer limited to 45 degree, unless you add a cleanout. 90 degree change is made with two 45 degree ell. |