Permit: T13CM05368

Parcel: 123090100


Addresses:

3033 E MABEL ST #2

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/06/2013 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/05/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection 1. At the shower- horizontal dry vent not permitted per the IRC. 3" quarter bend not permitted horizontal X horizontal. Changes in direction in the building drain and sewer limited to 45 degree, unless you add a cleanout. 90 degree change is made with two 45 degree ell.