Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2013 | ELECTRIC - RECONNECT | Approved | ||
| 09/10/2013 | ELECTRIC - RECONNECT | Denied | BREAKER MANUFACTURER MUST MATCH PANEL MANUFACTURER | |
| 09/04/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/04/2013 | ELECTRIC - RECONNECT | Denied | 1. CLEAN UP EXPOSED WIRING FUSE BOX IN CLOSET NEXT TO WASHROOM & BEHIND STOVE, LIVINGROOM, BACK BEDROOM 2. BOND WATER/GAS PIPING 3. 1/4" MIN BOLTS FOR CONDUIT RISER SUPPORT. #8 SCREWS TOO SMALL |
|
| 08/23/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |