Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2014 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/19/2014 |
MECHANICAL - FINAL |
|
Approved |
COAT EXPOSED PVC W/ LATEX PAINT. GAS REGULATOR VENTS TO BE MIN 3' FROM A/C UNITS. PROVIDE GASKETS AT EXHAUST FANS. PROVIDE A GREASE RECEPTOR AT EF-4. CAP-OFF VENT UPSTREAM OF CONDENSATE TRAP. GAS FLEX CONNECTORS NOT SIZED CORRECTLY. HEAT SENSOR TEST IS OK. CAPTURE & CONTAINMENT TEST IS OK. |
| 03/18/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |