Permit: T13CM05208

Parcel: 12712267A


Addresses:

5725 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T13CM05208

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/25/2014 PLUMBING - FINAL Approved IVRS - Inspection :*
03/21/2014 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
03/21/2014 PLUMBING - FINAL Partial Approval INSTALL VACUUM BREAKER AT SINK K-58 MIN 6" ABOVE FLOOD LEVEL OF SINK. PROVIDE DOME STRAINERS AT FLOOR SINKS. PROVIDE APPROVED PLUGS AT CLEANOUTS. SECURE ALL DRAIN PIPING UNDER SINKS. BACKFLOW FOR COFFEE & TEA TO BE SEPARATE FROM CARBONATORS. BACKFLOW HEIGHT TO BE PER MANUFACTURERS INSTALL INSTRUCTIONS. EACH CARBONATOR REQUIRES A SEPARATE BACKFLOW DEVICE. SECURE MIXING VALVES UNDER LAVS. PROVIDE ACCESS TO TRAP PRIMER. PROVIDE CHECK VALVES AT RECIRCULATING PUMPS. PAINT EXPOSED PVC ON ROOF. CAP-OFF VENTS AT CONDENSATE TRAPS.
03/18/2014 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/05/2014 PLUMBING - FINAL Partial Approval IVRS - Inspection :*