Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T13CM05208
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/25/2014 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
03/21/2014 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
03/21/2014 | PLUMBING - FINAL | Partial Approval | INSTALL VACUUM BREAKER AT SINK K-58 MIN 6" ABOVE FLOOD LEVEL OF SINK. PROVIDE DOME STRAINERS AT FLOOR SINKS. PROVIDE APPROVED PLUGS AT CLEANOUTS. SECURE ALL DRAIN PIPING UNDER SINKS. BACKFLOW FOR COFFEE & TEA TO BE SEPARATE FROM CARBONATORS. BACKFLOW HEIGHT TO BE PER MANUFACTURERS INSTALL INSTRUCTIONS. EACH CARBONATOR REQUIRES A SEPARATE BACKFLOW DEVICE. SECURE MIXING VALVES UNDER LAVS. PROVIDE ACCESS TO TRAP PRIMER. PROVIDE CHECK VALVES AT RECIRCULATING PUMPS. PAINT EXPOSED PVC ON ROOF. CAP-OFF VENTS AT CONDENSATE TRAPS. | |
03/18/2014 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/05/2014 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* |