Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/17/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/17/2013 | BUILDING - FINAL | Denied | PROVIDE THE MINIMUM REQUIRED CLEARANCES FROM ROOF EDGES. SECURE ALL CONDUITS. LABEL ALL CONDUITS. NEC 690.31, IFC 605. PROVIDE ALL REQUIRED LABELS. CORRECT PANEL DEAD FRONT. MOCE RAIN WATER TANK BLOCKING ACCESS TO MAIN PANEL. CORRECT BROKEN SCREW & LOOSE WIRES. REMOVE DEBRIS IN DISCONNECT BOX. **INSPECTION STOPPED** |