Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13CM05156
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2014 | FIRE SPKLR - FINAL | Approved | ||
08/20/2014 | FIRE SPKLR - FINAL | Denied | OKAY to close up ceilings Check overhangs in Lou of insulation they cover areas with sprinklers need to change plans to reflect what's on site. Still need to see above loading dock area. Kitchen area was corrected OKAY to close up ceilings |
|
08/13/2014 | FIRE SPKLR - FINAL | Denied | OKAY TO COVER CEILING MAIN FLOORS 200 PSI TEST FOR 2 HOURS APPROVED 1. Need as builts for changes on approved sprinkler plans bubble all changes on plans and why changes were made. a. In dining room pendants were to be used but now changed to sidewalls x 6. b. Upright coverage southwest corner above kitchen hood dead pocket space need to add a head. c. Correct sprinkler coverage above coolers Westside missing one upright head. d. Correct requirements for the eaves completely fill with insulation or add proper sprinkler coverage. 2. Need to see upright coverage in loading dock area, all covered up by plywood. |