Permit: T13CM05156

Parcel: 12510003G


Addresses:

3455 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13CM05156

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2014 FIRE SPKLR - FINAL Approved
08/20/2014 FIRE SPKLR - FINAL Denied OKAY to close up ceilings
Check overhangs in Lou of insulation they cover areas with sprinklers need to change plans to reflect what's on site.
Still need to see above loading dock area.
Kitchen area was corrected
OKAY to close up ceilings
08/13/2014 FIRE SPKLR - FINAL Denied OKAY TO COVER CEILING MAIN FLOORS
200 PSI TEST FOR 2 HOURS APPROVED
1. Need as builts for changes on approved sprinkler plans bubble all changes on plans and why changes were made.
a. In dining room pendants were to be used but now changed to sidewalls x 6.
b. Upright coverage southwest corner above kitchen hood dead pocket space need to add a head.
c. Correct sprinkler coverage above coolers Westside missing one upright head.
d. Correct requirements for the eaves completely fill with insulation or add proper sprinkler coverage.
2. Need to see upright coverage in loading dock area, all covered up by plywood.