Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
05/29/2014 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/30/2013 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/30/2013 ELECTRIC - UNDERGROUND Partial Approval FLOOR BOX AT LIVING ROOM OK TO COVER