Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/11/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/11/2013 | ELECTRIC - FINAL | Not ready for Inspection | CANCELED PER ANGIE | |
| 09/23/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/23/2013 | ELECTRIC - FINAL | Denied | 1. EXPOSE GROUNDING ELECTRODE SYSTEM AT FRONT UNIT FOR INSPECTION 2. CANNOT USE ALL IN ONE AS SUB-PANEL AS PER LISTING. EXPOSED U.G. SHOULD BE 18" DEEP 3. NEUTRAL MUST BE BONDED AT SERVICE ENCLOSURE 4. BUSHING REQUIRED AT CONDUIT TERMINATION 5. BOND BUSHING IN METER BASE **USE LICENSED ELECTRICIAN TO DO WORK** |
|
| 08/23/2013 | ELECTRIC - FINAL | Partial Approval | RE OPENED PERMIT PER TEP REQUEST FOR RE INSPECTION ON MOVED DISCONNECT ON UNIT 2. ANOTHER CLEARANCE IS REQUESTED PER TEP. |