Permit: T13CM05033

Parcel: 120060470


Addresses:

3815 S 5TH AV #03

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/09/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/08/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/08/2013 ELECTRIC - FINAL Denied BACK FED CKT BREAKERS REQUIRE HOLD DOWN KIT. AS PER ART 408 NEC, AND MUST BE LISTED
10/03/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/03/2013 ELECTRIC - FINAL Denied 1. NEW BREAKER PANEL SUITABLE FOR USE AS SERVICE EQUIP WHEN MAIN CRT BREAKER INCULDED - SEE INSTRUCTIONS INSIDE COVER
2. MUST USE SAM MANUF CRT BREAKERS AS PANEL PER LISTING. USE QUALIFIED ELECTRICIAN TO DO WORK
3. VERIFY WATER & GAS PIPE BONDING
4. USE CORRECT FITTINGS FOR CONNECTION BETWEEN PANEL & METER BASE
09/25/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/25/2013 ELECTRIC - FINAL Denied 1. EXTERIOR PANEL IS BURNT OUT, REPAIR OR REPLACE
2. REMOVE THREADS FROM END OF T.P.R. PIPING
09/03/2013 ELECTRIC - FINAL Not ready for Inspection CALL FOR FINAL INSPECTION AFTER
1. REPAIR OF SINK HOLE
2. SECURE LOOSE OUTLET BOXES IN BACK & ROMEX IN RACEWAY DOWN WALL
3. VERIFY WATER & GAS PIPE BONDING

OK TO CLEAR RECN ONLY UNIT 3, NO FINAL APPROVAL AT THIS TIME
08/19/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/19/2013 ELECTRIC - FINAL Denied - GROUND WIRE CUT FOR ELECTRIC SERVICE, REGROUND SYSTEM PER 250 NEC.
- WATER HTR MISSING OVERFLOW PIPING AT RELIEF VALVE
- REPAIR AS NECESSARY AT SINK HOLE IN BACK