Permit: T13CM04952

Parcel: 13216639A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM04952

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2013 FIRE - FINAL Approved
11/07/2013 FIRE - FINAL Partial Approval Temp C of O approved okay to use building, to get final C of O need to add sprinkler coverage under conveyors permit for sprinkler will need to be closed also.
Sprinkler reports are in and no problems shown.
Fire extinguishers are in place and proper type.
10/28/2013 FIRE - FINAL Denied 1. Need fire extingushers 1 for 1500 sq feet and 75 foot travel distance a 2-A 10BC type.
2. Need sprinkler and 5 year check valve inspection completed, field notice given.
3. Add sprinkler coverage under new conveyors.