Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2013 | PLUMBING - FINAL | Not ready for Inspection | CARBON MONOXIDE & FURNCO | |
| 08/23/2013 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/22/2013 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/22/2013 | PLUMBING - FINAL | Not ready for Inspection | - REPLACE DAMAGED "B" VENT - CODE REQUIRES A CARBON MONOXIDE DETECTOR - FURNCO COUPLING IN WALL |
|
| 08/16/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/15/2013 | PLUMBING - FINAL | Denied | REMOVE ADHESIVE TAPE FROM PEX. SEE YOUR INSULATION INSTRUCTIONS. ISOLATE PEX FROM BLOCK WALL & NAIL PLATES. ISOLATE OR SECURE PEX FROM SHEETROCK FOR NOISE. CAP ANY OPEN DRAIN PIPES FOR SAFETY. (SEWER GASSES) PROVIDE 18" OF COPPER UPSTREAM OF SWEAT VALVE & WATER HEATER. USE THREAD SEALANT ON MALE THREADS. WIPE CLEAN ANY EXCESS FLUX ON SOLDIER JOINTS. PROVIDE A LISTED TEE AT COMBINATION VENT. PROVIDE CLEARANCE AROUND "B" VENT. HB VACUUM BREAKERS? HAMMER ARRESTORS. ALSO, FERNCO NOT ALLOWED PROFLEX OR MISSION REQ |