Permit: T13CM04795

Parcel: 13322500E


Addresses:

7125 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/07/2013 FIRE - FINAL Approved
10/25/2013 FIRE - FINAL Denied 1. Duct detectors need to be rewired.
2. Okay to stock.
09/11/2013 FIRE - FINAL Denied 1. Fire shall be install every 75' foot travel distance 2A-10BC type
2. Need to install a fire alarm system will need a separate approved plan and permit for this work.
3. Install F.D. key box for the riser room access.
4. Need a 1 inch plane above the upright sprinkler coverage get all insulation 1 inch above the sprinkler coverage.
5. Need an annual sprinkler inspection and 5 year check valve inspection completed.
6. Label riser room door "RISER ROOM"