Permit: T13CM04737

Parcel: 13322424B


Addresses:

7055 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T13CM04737

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/12/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
11/08/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
11/08/2013 MECHANICAL - FINAL Partial Approval PROVIDE MIN 3" OVERLAPS ON FIRE WRAP. INSULATE ACCESS DOORS PER INSTALL INSTRUCTIONS. TIGHTEN BANDS WITH THE PROPER TOOL. ADD BANDING WHERE NEEDED. OVEN NOT FUSED PER PLAN. RELOCATE HORIZONTAL DRAIN FROM SINK. COVER PLATE MISSING FROM J BOX UNDER COUNTER. PROVIDE BACKFLOW CERTS AS NEEDED. PROVIDE A HINGE KIT ON EXHAUST FAN. FINISH CONDENSATE CONNECTIONS.