Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T13CM04737
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/25/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/12/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
11/12/2013 | ELECTRIC - FINAL | Partial Approval | PROVIDE STERILIZATION REPORT. PROVIDE PANEL SCHEDULES. SHOW HOW A/C UNIT & POWER EXHAUSTER ARE BOTH FUSED AT 15 AMP MAX. SEPARATELY. BUSHING AT CONNECTION TO A/C UNIT NOT COVERING ALL KNOCKOUTS. NEED TO SEE INTERLOCK AT OVEN & FAN. PAINT EXPOSED PVC W/ LATEX PAINT. CAPTURE & CONTAINMENT OK. NEED AIR BALANCE REPORT. | |
11/08/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |