Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/25/2013 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 11/12/2013 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 11/12/2013 |
ELECTRIC - FINAL |
|
Partial Approval |
PROVIDE STERILIZATION REPORT. PROVIDE PANEL SCHEDULES. SHOW HOW A/C UNIT & POWER EXHAUSTER ARE BOTH FUSED AT 15 AMP MAX. SEPARATELY. BUSHING AT CONNECTION TO A/C UNIT NOT COVERING ALL KNOCKOUTS. NEED TO SEE INTERLOCK AT OVEN & FAN. PAINT EXPOSED PVC W/ LATEX PAINT. CAPTURE & CONTAINMENT OK. NEED AIR BALANCE REPORT. |
| 11/08/2013 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |