Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T13CM04737

Parcel: 13322424B


Addresses:

7055 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/25/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/12/2013 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/12/2013 ELECTRIC - FINAL Partial Approval PROVIDE STERILIZATION REPORT. PROVIDE PANEL SCHEDULES. SHOW HOW A/C UNIT & POWER EXHAUSTER ARE BOTH FUSED AT 15 AMP MAX. SEPARATELY. BUSHING AT CONNECTION TO A/C UNIT NOT COVERING ALL KNOCKOUTS. NEED TO SEE INTERLOCK AT OVEN & FAN. PAINT EXPOSED PVC W/ LATEX PAINT. CAPTURE & CONTAINMENT OK. NEED AIR BALANCE REPORT.
11/08/2013 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*